FLP-7-V/1+1 Combined Lightning & Surge Arrester

FLP-7-V/1+1 Combined Lightning & Surge Arrester

Product Details:

X

Product Description

Lightning Current Arresters

FLP-7-V/1+1

FLP-7-V/1S+1

SPD type 1 and type 2

2-pole (1+NPE) arrester for single phase TT (TNS) networks Varistor lightning and surge current arrester and heavy duty encapsulated spark gap in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version „S“. * Version UC =385 V available on request

 

Technical data

L-N

N-PE

Nominal voltage Un

230 V AC

-------

Maximum operating voltage Uc

275 V AC

255 V AC

Nominal discharge current (8/20 μs) In

30 kA

30 kA

Maximum discharge current (8/20 μs) Imax

60 kA

60 kA

Lighting impulse current (10/350 μs) Iimp

7 kA

25 kA

Voltage protection level Up

1,2 kV

1,5 kV

Voltage protection level (L - PE) Up

                                                        1,5 kV

 

Response time ta

25 ns

25 ns

Ability to independently switch off the following current Ifi

no following current

100 A

Short-circuit proof at maximum overcurrent protection

50 kArms

----------

Maximum overcurrent protection

160 A gL/gG

----------

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid min/max

Stranded min/max

 

ISO: 1/35 mm2 ; AWG: 17/2

ISO: 1/25 mm2 ; AWG: 17/4

 

ISO: 1/35 mm2 ; AWG: 17/2

ISO: 1/25 mm2 ; AWG: 17/4

Fault indication

red indication field

ne

Remote indication – S design

potential-free change-over contact

-------

Remote indication contacts

250 V / 0,5 A AC, 250 V / 0,1 A DC

-------

Cross-section of remote indication conductors

max. 1,5 mm2

-------

Meets the requirements of standard

IEC 61643-11 ed. 1.0T1T2

EN 61643-11:2012T1T2

IEC 61643-11 ed. 1.0T1T2

EN 61643-11:2012T1T2


SABO SYSTEMS PVT. LTD.

* Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.

Other Products in 'Lightning Conductor Installation Accessories' category



Banarsi Complex, First Floor, Faizabad Road, Opp. SBI Nishatganj Branch, Lucknow - 226006, Uttar Pradesh, India
Phone :+918045801119
Mr Pawan Kumar Agarwal (Director)
Mobile :918045801119
Paypal Trust Stamp
Product Showcase
Send Inquiry Send SMS